Headquarters
N56 W16665 Ridgewood Dr. Menomonee Falls, WI 53051
Meet battery room ventilation safety requirements and create an automated hydrogen gas ventilation system using the SBS Exhaust Fan in conjunction with the SBS-H2 hydrogen gas detector. This 12" x 12" fan automatically vents out dangerous hydrogen gas that builds up in battery charging rooms/areas.
The flexible fan design, featuring a sliding collar, works on walls between 1.5" and 8" thick, allowing for easy installation. The fan is weather resistant due to fixed external louvers with motor-driven internal louvers.
Part No. | Description |
H2FAN-12x12-110VAC | 12" x 12" Exhaust Fan, 110 Vac Input |
H2FAN-12x12-24VDC | 12" x 12" Exhaust Fan, 24 Vdc Input |
H2FAN-12x12-48VDC | 12" x 12" Exhaust Fan, 48 Vdc Input |
Weight | 18.000000 |
Airflow | 850 CFM |
Mounting | Rough opening: 12.25" x 12.25" (311 x 311 mm) Wall thickness: 1.5" to 8" (38 x 203 mm) |
Power Supply(s) | 110 Vac, .67 Amps (80 Watts) 24 Vdc, 3.5 Amps 48 Vdc, 1.7 Amps |
Dimensions | 12" L x 12" W x 9.5" D (305 x 305 x 241 mm) |